AP Modular 20-300KW [On Line Modular UPS]

+Power Modular UPS Offering high efficiency and overload capability, +Power is a truly modular UPS system which can easily scales in 30kW increments up to 210kW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.

  • Output power factor 1

  • N+1 or N+R Parallel Redundancy for power guarantee

  • Modular design decreases MTTR

  • High scalability

  • High reliable operation with redendant power supply in STS

  • Built-in maintenance bypass switch for easy maintenance without interruptible

  • High efficiency double conversion online UPS

  • Adjustable battery numbers

  • User-adjustable charging current

  • Graphic 5.7'' LCD design for easy configuration

Drag the table to right or left to view more.
MODEL+AP 30U-90HV+AP 42U-120HV+AP 30U-120HV
+AP 30U-80-20KHV
+AP 30U-180HV
+AP 30U-120-20KHV
+AP 42U-200-20KHV+AP 42U-210HV+AP 42U-300HV
PHASE3-phase in/3-phase out
CABINET CAPACITY*90KW120KW120KW or 80KW180KW or 120KW200KW210KW300KW
BATTERY TYPEBuilt-in BatteryExternal Battery
One Power Module Capacity30KVA/30KW30KVA/30KW or 20KVA/20W20KW30KVA/30KW30KVA/30KW
Max. Power Module No.344610810
Max. Battery Set No.**35-----
INPUT
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N) 
Voltage Range 305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load
Nominal Frequency 50/60Hz (Auto sensing)
Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)< 3% @ 100% load
OUTPUT
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N) 
Voltage Regulation (Steady state)≦± 1% Typical (balanced load) 
       ≦± 2% Typical (unbalanced load)
Nominal Frequency 50/60Hz
Frequency Range (Synchronized range)46Hz ~ 54Hz or 56Hz ~ 64Hz 
Overload Capability 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Harmonic Distortion≦ 2% THD (Linear Load)
       ≦ 4% THD (Non-linear Load)
Efficiency Up to 94.5%
BATTERY / CHARGER
Nominal Voltage +/-  216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Floating Charge Voltage 2.25V/Cell
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module)8A8A for 30KW power module
       6A for 20KW power module
6A8A8A
PHYSICAL
Cabinet Dimension 
       (D x W x H) mm
1100 x 600 x 1475 1100 x 600 x 20101100 x 600 x 1475 1100 x 600 x 1475 1100 x 600 x 2010
Net Weight (kgs)675932335 or 333437.5 or 434.5611549620
ENVIRONMENT
Operation Temperature 0 ~ 40℃
Relative Humidity 0 ~ 95% non-condensing
Altitude ***<1000m for Nominal power
IP Class IP 20
MANAGEMENT
RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
STANDARDS
SafetyIEC/EN 60950-1; IEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3
*When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃. 
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules. 
***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.