KEBOS POWER ,to continue a better life.
Embedded with isolation transformer, it will eliminates common mode noise and the need to install expensive dedicated circuits.
GL 31 Lite series Three phase in and Single phase out Low Frequency UPS provides reliable galvanically isolated power to critical equipment.
Galvanic isolation design to withstand all kinds of loads
Output power factor 0.8
Fully coating PCBAs to withstand harsh environment
Unique ventilation design for effective heat dissipation
Wide input voltage and frequency range to withstand robust environment
High short-circuit and overload capabilities
Built-in Maintenance bypass switch
MODEL | GL31 Lite-6K(L) | GL31 Lite-7.5K(L) | GL31 Lite -10K(L) | |||||
---|---|---|---|---|---|---|---|---|
PHASE | 3-phase in / 1-phase out | |||||||
CAPACITY* | 6KVA/4.8KW | 7.5KVA/6KW | 10KVA/8KW | |||||
INPUT | ||||||||
Nominal Voltage | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) | |||||||
Acceptable Voltage Range | 286VAC ~ 493VAC @ 16 pcs of batteries 320VAC ~ 493VAC @ 18 pcs of batteries | |||||||
Frequency | 40Hz ~ 55 Hz @ 50Hz system 56 Hz ~ 64Hz @ 60Hz system | |||||||
OUTPUT | ||||||||
Output Voltage | 208VAC/220VAC/230VAC (Selectable) | |||||||
Voltage Regulation | ±1% | |||||||
Frequency Range | 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz | |||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | |||||||
Current Crest Ratio | 3:1 | |||||||
Harmonic Distortion | <3% (Linear Load) <5% (Non-linear Load) | |||||||
Transfer Time | AC to DC | Zero | ||||||
Inverter to Bypass | Zero | |||||||
Wave Form (Batt. Mode) | Pure Sine Wave | |||||||
Efficiency | ||||||||
Line Mode | 83% | |||||||
Battery Mode | 92% | |||||||
INDICATORS | ||||||||
LCD | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code | |||||||
ALARM | ||||||||
Battery Mode | Sounding every 4 seconds | |||||||
Low Battery | Sounding every second | |||||||
Overload | Sounding twice every second | |||||||
Fault | Continously sounding | |||||||
BATTERY | ||||||||
Standard Model | Battery Type | 12V / 9Ah | ||||||
Battery Numbers** | 16pcs | 16pcs | 16pcs | |||||
Recharge Time | 6 hours recovers to 90% capacity | |||||||
Charging Current | 2A | |||||||
Charging Voltage | 218.4 V ± 1% | 218.4 V ± 1% | 218.4 V ± 1% | |||||
Long-run Model | Battery Type | Depending on the applications | ||||||
Battery Numbers** | 16pcs | 18 pcs | 16pcs | 18 pcs | 16pcs | 18 pcs | ||
Charging Current | Default: 8A, 2A/4A/8A(adjustable) | |||||||
Charging Voltage | 218.4 V ± 1% | 245.7 V ± 1% | 218.4 V ± 1% | 245.7 V ± 1% | 218.4 V ± 1% | 245.7 V ± 1% | ||
PHYSICAL | ||||||||
Standard Model | Dimensions, D x W x H(mm) | 592 x 300 x 826 | 592 x 360 x 826 | 592 x 300 x 826 | 592 x 360 x 826 | 592 x 300 x 826 | 592 x 360 x 826 | |
Net Weight (Kgs) | 129 | 137 | 152 | 160 | 160 | 168 | ||
Long-run Model | Dimensions, D x W x H(mm) | 592 x 300 x 826 | ||||||
Net Weight (Kgs) | 84 | 107 | 115 | |||||
ENVIRONMENT | ||||||||
Operating Temperature | 0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C) | |||||||
Humidity | <95 % and non-condensing | |||||||
Noise Level | Less than 60dBA @ 1 Meter | |||||||
MANAGEMENT | ||||||||
Modbus RS-232/RS485 | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC | |||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||
* Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC. | ||||||||
**Battery number is set in factory and can't be changed by users. | ||||||||
Product specifications are subject to change without further notice |