KEBOS POWER ,to continue a better life.
GH33 III series Online UPS from 30K -200KVA, is specially designed with pluggable power module and front access to simplify maintenance. Its power walk-in function optimize parallel operation up to 6 units even with generator input.
ECO mode operation for energy saving (ECO)
Emergency power off function (EPO)
Generator compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers for long-run model
Maintenance bypass available
Parallel operation with common battery
Power walk-in function
Optional isolation transformer offers full isolation and complete common mode noise rejection
MODEL | GH33 III -30 KL | GH33 III -40KL | GH33 III -60 KL | GH33 III -100KL | GH33 III -120KL | GH33 III -180KL | GH33 III -200KL | |
---|---|---|---|---|---|---|---|---|
PHASE | 3-phase in/3-phase out | |||||||
CAPACITY | 30KVA / 30KW | 40KVA/40KW | 60KVA / 60KW | 100KVA / 100KW | 120KVA / 120KW | 180KVA / 180KW | 200KVA / 200KW | |
PARALLEL CAPABILITY | 4 | |||||||
INPUT | ||||||||
Nominal Voltage | 3 x 360/380/400/415 VAC (3Ph+N) | |||||||
Voltage Range | 110-300 VAC @ 50% load ; 176-276 VAC @ 100% load | |||||||
Frequency Range | 40~70 Hz | |||||||
Power Factor | ≧ 0.99 @ 100% load | |||||||
Harmonic Distortion (THDi) | < 4% at full linear load | |||||||
OUTPUT | ||||||||
Output Voltage | 3 x 360*/380*/400/415 VAC (3Ph+N) | |||||||
AC Voltage Regulation (Batt. Mode) | ± 1% | |||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||||||
Frequency Range (Batt. Mode) | 50/60 Hz ± 1% | |||||||
Current Crest Ratio | 3:1 (max.) | |||||||
Harmonic Distortion | ≦2% THD (Linear Load) ≦5% THD (Non-linear Load) | |||||||
Transfer Time | AC mode to Battery mode | zero | ||||||
Inverter to Bypass | zero | |||||||
Wave Form (Batt. Mode) | Pure Sine Wave | |||||||
Overload Capability | 100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% immediately shutdown | |||||||
BYPASS | ||||||||
Nominal Voltage | 3 x 360/380/400/415 VAC (3Ph+N) | |||||||
Voltage Range | 305VAC~457VAC | |||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||||||
Overload Capability | > 130% 1 minute (default) Continously working until breaker protection (optional) | |||||||
EFFICIENCY | ||||||||
AC Mode | 95.5% | |||||||
ECO Mode | 98.5% | |||||||
Battery Mode | 94.5% | |||||||
BATTERY | ||||||||
Battery Type | Depending on application | |||||||
Numbers | 32~40 pcs (Adjustable) | |||||||
Charging Current (max.) | 1-12A, Adjustable | 1-18A, Adjustable | 2-36A, Adjustable | 3-54A, Adjustable | ||||
Charging Voltage | +/-13.65V*N (N = 16~20) | |||||||
INDICATORS | ||||||||
Touch color LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||||||
ALARM | ||||||||
Battery Mode | Sounding every 4 seconds | |||||||
Low Battery | Sounding every second | |||||||
Overload | Sounding twice every second | |||||||
Fault | Continuously sounding | |||||||
PHYSICAL | ||||||||
Dimension, D X W X H (mm) | 815 x 300 x 1000 | 815 x 300 x 1000 | 974 x 600 x 1600 | |||||
Net Weight (kgs) | 74 | 54 | 87 | 250 | 250 | 340 | 345 | |
ENVIRONMENT | ||||||||
Operation Temperature | 0-40°C | |||||||
Operation Humidity | <95% and non-condensing | |||||||
Altitude** | 0 ~ 1000m at full load | |||||||
Noise Level | Less than 65 dB @ 1 Meter | Less than 70 dB @ 1 Meter | Less than 75 dB @ 1 Meter | |||||
MANAGEMENT | ||||||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC | |||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||
*When output voltage is set as 3 x 360VAC or 3 x 380VAC, the output power of the unit will be de-rated to 90%. | ||||||||
**If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m. | ||||||||
Product specifications are subject to change without further notice. |