AP Lite 15U 60-90K is a modular UPS system comprised of 1 to 3 modules of 30KW. This UPS is easily upgraded by users through adding plug-and play 30kw power modules. Beside, this UPS system is stacked with battery pack as a tower for smaller footprint. It’s a perfect power solution for small-to-medium enterprise.
High efficiency online double conversion technology
Output power factor 1
Modular design lowers MTTR
Adjustable battery numbers
Adjustable charging current
Built-in maintenance bypass switch for easy maintenance without interruptible
Graphic 5.7" LCD design for easy configuration
| MODEL | AP Lite 15U-60 | AP Lite 15U-90 |
|---|---|---|
| PHASE | 3-phase in/3-phase out | |
| CABINET CAPACITY* | 60KW | 90KW |
| BATTERY TYPE | External Battery | |
| One Power Module Capacity | 20KVA/20KW | 30KVA/30KW or 20KVA/20KW |
| Max. Power Module No. | 3 | |
| INPUT | ||
| Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | |
| Voltage Range | 305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load | |
| Nominal Frequency | 50/60Hz (Auto sensing) | |
| Frequency Range | 40Hz ~70Hz | |
| Power Factor | > 0.99 at 100% load, >0.98 at 50% load | |
| Harmonic Distortion (THDi) | < 3% @ 100% load | |
| OUTPUT | ||
| Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | |
| Voltage Regulation (Steady state) | ≦± 1% Typical (balanced load) ≦± 2% Typical (unbalanced load) | |
| Nominal Frequency | 50/60Hz | |
| Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |
| Overload Capability | 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% | |
| Harmonic Distortion | ≦ 1.5% THD (Linear Load) ≦ 4% THD (Non-linear Load) | |
| Efficiency | Up to 94.5% | |
| BATTERY / CHARGER | ||
| Nominal Voltage | +/- 216V (12V x 36 Pcs) | |
| Maximum Voltage | +/- 240V (12V x 40 Pcs) | |
| Minimum Voltage | +/- 192V (12V x 32 Pcs) | |
| Floating Charge Voltage | 2.25V/Cell | |
| Boost Charging Voltage | 2.35V/Cell | |
| Temperature Compensation | Yes | |
| Maximum Charging Current (Per Power Module) | 8A for 30KW power module (User-djustable) 6A for 20KW power module (User-adjustable) | |
| PHYSICAL | ||
| Cabinet Dimension (D x W x H) mm | 1000 x 515 x 760 | |
| Net Weight (kgs) | 182 | 183.5 |
| ENVIRONMENT | ||
| Operation Temperature | 0 ~ 40℃ | |
| Relative Humidity | 0 ~ 95% non-condensing | |
| Altitude *** | <1000m for Nominal power | |
| IP Class | IP 20 | |
| MANAGEMENT | ||
| RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | |
| Optional SNMP | Power management from SNMP manager and web browser | |
| STANDARDS | ||
| Safety | IEC/EN 60950-1; IEC/EN 62040-1 | |
| EMC | IEC/EN 62040-2 Category C3 | |
| *When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃. | ||
| ** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules. | ||
| ***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m. | ||
| Model | Description | Dimension DxWxH(mm) | Weight (kg) |
|---|---|---|---|
| PM-30HV | 3P/3P 30KVA/30KW power module | 650x440x132(3U) | 34.5 |
| PM-20HV | 3P/3P 20KVA/20KW power module | 650x440x132(3U) | 34 |
| Battery Cabinet | 120 pcs of 12V9Ah batteries | 1000 x 514 x 610 | 387 |