KEBOS POWER ,to continue a better life.
GR33 10-60K is the high density version of double-conversion online UPS. With an output power factor 0.9 and 91% operating efficiency in online mode, it's suitable for powering a wide range of devices such as servers, data center, industrial processes,telecommunication and security system. Besides, it is provided with input power factorcorrection function that helps to avoid any damageto the mains and also facilitate the connection of generator.
True double-conversion
DSP technology guarantees high performance
Output power factor 1
Wide input voltage range (110-300 VAC)
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
Eco mode operation for energy saving (ECO)
Accepts dual power inputs
Emergency power off function (EPO)
Generator compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers
Maintenance bypass available
Optional N+X parallel redundancy
Optional isolation transformer offers full isolation and complete common mode noise rejection
MODEL | GR33-10KL | GR33-15KL | GR33-20KL | GR33-30KL | GR33-40KL | GR33-60KL | |
---|---|---|---|---|---|---|---|
PHASE | 3-phase in/3-phase out | ||||||
CAPACITY | 10KVA/10KW | 15KVA/15KW | 20KVA/20KW | 30KVA/30KW | 40KVA/40KW | 60KVA/60KW | |
PARALLEL CAPABILITY | 4 | ||||||
INPUT | |||||||
Nominal Voltage | 3 x 400 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N) | ||||||
Voltage Range | 190-520 VAC (3-phase) @ 50% load 305-478 VAC (3-phase) @ 100% load | ||||||
Frequency Range | 46~54 Hz or 56~64Hz | ||||||
Power Factor | ≧ 0.99 @ 100% load | ||||||
OUTPUT | |||||||
Output Voltage | 3 x 360*/380/400/415 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N) | 3 x 360*/380/400/415 VAC (3Ph+N) | |||||
AC Voltage Regulation (Batt. Mode) | ± 1% | ||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | ||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||||
Current Crest Ratio | 3:1 (max.) | ||||||
Harmonic Distortion | ≦ 2 % THD (Linear Load) ≦ 5 % THD (Non-linear Load) | ||||||
Transfer Time | AC mode to Battery mode | zero | |||||
Inverter to Bypass | zero | ||||||
Wave form (Batt. Mode) | Pure Sine Wave | ||||||
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately | |||||
Battery Mode | 100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately | ||||||
EFFICIENCY | |||||||
AC Mode | 95.5% | ||||||
ECO Mode | 98.5% | ||||||
Battery Mode | 94.5% | ||||||
BATTERY | |||||||
Battery Type | Depending on the applications | ||||||
Numbers | 20 pcs | 32~40 pcs (Adjustable) | |||||
Charging Current (max.) | 1A ~ 12A (Adjustable) | 1A ~ 16A (Adjustable) | 1A ~ 18A (Adjustable) | ||||
Charging Voltage | +/-13.65 VDC x N (N=10) | +/-13.65V x N (N=16~20) | |||||
PHYSICAL | |||||||
Dimension, D X W X H (mm) | 680 x 438 x 133 [3U] | 797 x 438 x 176(4U) | |||||
Net Weight (kgs) | 26 | 28 | 28 | 35 | 40 | 45 | |
ENVIRONMENT | |||||||
Operation Temperture | 0-40°C | ||||||
Operation Humidity | <95% and non-condersing | ||||||
Noise Level | Less than 62dB @ 1 Meter | Less than 65dB @ 1 Meter | Less than 65dB @ 1 Meter | Less than 65dB @ 1 Meter | Less than 70dB @ 1 Meter | ||
MANAGEMENT | |||||||
Smart RS-232/USB | Supports Windows® family, Linux and MAC | ||||||
Optional SNMP | Power management from SNMP manager and web browser | ||||||
*When output voltage is set as 3 x 360VAC or 208 VAC, the output power of the unit will be de-rated to 90%. | |||||||
Product specifications are subject to change without further notice |