KEBOS POWER ,to continue a better life.

GR11 One 6-10KVA

With True Double-Conversion design, GR11 One 6KVA-10KVA  series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. Its perfect protection for your precious servers and workstations. For GR 11 Pro 6K-10K RT with cTUVus, please check with our sales.

  • True double-conversion

  • DSP technology guarantees high performance

  • Output Power Factor 1

  • Wide input voltage range (110-300 VAC)

  • Active input power factor correction 0.99

  • 50Hz/60Hz frequency converter mode

  • Emergency power off function (EPO)

  • ECO mode for energy saving

  • Generator compatible

  • SNMP/USB/RS-232 communications

  • Adjustable battery numbers

  • Optional N+X parallel redundancy

Drag the table to right or left to view more.
MODELGR11 One 6K(L) GR11 One 10K(L) 
PHASE1 phase in / 1 phase out
CAPACITY6000 VA / 6000 W10000 VA / 10000 W
INPUT
Nominal Voltage208/220/230/240 VAC
Voltage Range 110~300VAC ± 3 % at 50% load
176~300VAC ± 3 % at 100% load 
Frequency Range46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
PhaseSingle phase with ground
Power Factor≧< 0.99  @ full load
THDi<4% @100%  Load, <6% @50% Load
OUTPUT
Output Voltage208*/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)± 1%
Frequency Range (Synchronized Range)46~54 Hz ◎ 50 Hz / 56~64 Hz ◎ 60 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio3:1 (max.)
Harmonic Distortion≦2% THD (Linear Load), ≦ 6 % THD (Non-linear Load)
Transfer TimeAC Mode to Batt. ModeZero
Inverter to BypassZero
Waveform (Batt. Mode)Pure Sine Wave
OverloadAC Mode100%~110%: 10min、110%~130%: 1min、>130% : 1sec
Battery Mode100%~110%: 30sec、110%~130%: 10sec、>130% : 1sec
EFFICIENCY
AC Mode94%
ECO Mode98.5%
Battery Mode92%
BATTERY
Standard ModelBattery Type12 V /9 AH12 V / 9 AH
Numbers1616
Typical Recharge Time9 hours recover to 90% capacity
Charging Current (max.)1.0 A
Charging Voltage 218.4 VDC ± 1%
Long-run ModelBattery TypeDepending on applications
Numbers20pcs
Charging Current (max.)4.0 A
Charging Voltage(13.65VDC x battery number) ± 1%
PHYSICAL
Standard ModelDimension, D X W X H (mm)UPS Unit: 610x438x88 [2U]
Battery Pack:715x438x88 [2U]
UPS Unit: 610x438x88 [2U]
Battery Pack: 715x438x88 [2U]
Net Weight (kgs)UPS Unit: 17
Battery Pack: 48
UPS Unit: 20
Battery Pack: 53
Long-run ModelDimension, D X W X H (mm)610 x 438 x 88 [2U]610 x 438 x 88 [2U]
Net Weight (kgs)1720
ENVIRONMENT
Operation Humidity20-90 % RH @ 0- 40°C (non-condensing)
Noise LevelLess than 55dBA @ 1 MeterLess than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232/USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC or parallel system is operated.
**When using 16 pieces of batteries, the output power factor will be derated to 0.8. If using 18 or 19 pieces of batteries, the output power factor will be derated to 0.9
***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice