KEBOS POWER ,to continue a better life.


True double-conversion
DSP technology guarantees high performance
Output power factor 1.0
Wide input voltage range (110-300 VAC)
Active input power factor correction 0.99
50Hz/60Hz frequency converter mode
Emergency power off function (EPO)
ECO mode for energy saving
Generator compatible
SNMP/USB/RS-232 communications
Adjustable battery numbers
Optional N+X parallel redundancy
| MODEL | KR11 Pro-6K(L) | KR11 Pro-10K(L) | |||
|---|---|---|---|---|---|
| PHASE | 1 phase in / 1 phase out | ||||
| CAPACITY | 6000 VA / 6000 W | 10000 VA / 10000 W | |||
| INPUT | |||||
| Nominal Voltage | 208/220/230/240 VAC | ||||
| Voltage Range | 110~300VAC ± 3 % at 50% load ; 176~300VAC ± 3 % at 100% load | ||||
| Frequency Range | 46~54 Hz or 56~64 Hz | ||||
| Power Factor | ≧ 0.99 @ full load | ||||
| THDi | <4% @100% Load, <6% @50% Load | ||||
| OUTPUT | |||||
| Output Voltage | 208*/220/230/240 VAC | ||||
| AC Voltage Regulation (Batt. Mode) | ± 1% | ||||
| Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz | ||||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||
| Current Crest Ratio | 3:1 (max.) | ||||
| Harmonic Distortion | ≦2 % THD (Linear Load), ≦6 % THD (Non-linear Load) | ||||
| Transfer Time | AC Mode to Batt. Mode | Zero | |||
| Inverter to Bypass | zero | ||||
| Wave Form (Batt. Mode) | Pure SineWave | ||||
| Overload | AC Mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | |||
| Battery Mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | ||||
| EFFICIENCY | |||||
| AC Mode | 94% | ||||
| Battery Mode | 92% | ||||
| BATTERY | |||||
| Standard Model | Battery Type | 12 V / 9 AH | 12 V / 9 AH | ||
| Numbers | 16 | ||||
| Typical Recharge Time | 9 hours recover to 90% capacity | ||||
| Charging Current (max.) | 1.0 A | ||||
| Charging Voltage | 218.4 VDC ± 1% | ||||
| Long-run Model | Battery Type | Depending on applications | |||
| Numbers | 16-20** | ||||
| Charging Current (max.) | 4.0 A | ||||
| Charging Voltage | (13.65VDC x battery number) ± 1% | ||||
| PHYSICAL | |||||
| Standard Model | Dimension, D X W X H (mm) | UPS Unit: 610x438x88 [2U] ; Battery Pack:715x438x88 [2U] | UPS Unit: 610x438x88 [2U] ; Battery Pack:715x438x88 [2U] | ||
| Net Weight (kgs) | UPS Unit: 17 ; Battery Pack: 48 | UPS Unit: 20 ; Battery Pack: 53 | |||
| Long-run Model | Dimension, D X W X H (mm) | 610 x 438 x 88 | 610 x 438 x 88 | ||
| Net Weight (kgs) | 17 | 20 | |||
| ENVIRONMENT | |||||
| Operation Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | ||||
| Noise Level | Less than 55dBA @ 1 Meter | Less than 58dB @ 1 Meter | |||
| MANAGEMENT | |||||
| Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC | ||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||
| * Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC or parallel system is operated. | |||||
| **When using 16 pieces of batteries, the output power factor will be derated to 0.8. If using 18 or 19 pieces of batteries, the output power factor will be derated to 0.9 | |||||
| ***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. | |||||
| * Product specifications are subject to change without further notice | |||||