KEBOS POWER ,to continue a better life.
- Industrial process (manufacturing and control system, Industrial machinery, instrument and measurement, process monitoring and control, security and transport systems….)
-Infrastructures (hospital, airport, semiconductor, water treatment, metallurgy)
-Energy industry (gas and oil, nuclear power)
-Military application
True online double conversion with DSP control
Galvanic isolation eliminates common mode noise and provides the cleanest power in the most demanding conditions
Conformal coating ensures operation stability and safety in critical environment
Standard IP31 protection, optional IP42 to withstand harsh environment
Wide range of operation temperature
In-built 40kA surge protection module
Redundant design on key components
High short-circuit and overload capabilities
Accepts dual-mains inputs
Parallel capability up to 4 units
MODEL | GL31 iND II 31-10K | GL31 iND II 31-20K | GL31 iND II 31-30K | GL31 iND II 31-40K | GL31 iND II 31-60K | GL31 iND II 31-80K | GL31 iND II 31-100K | GL31 iND II 31-120K | ||
---|---|---|---|---|---|---|---|---|---|---|
CAPACITY | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | 100KVA/80KW | 120KVA/96KW | ||
INPUT | ||||||||||
Rectifier Type | 6 pulse or 12 pulse | |||||||||
Main Input and Bypass Input | Supports dual inputs | |||||||||
Nominal Voltage | 380VAC/400VAC/415VAC | |||||||||
Acceptable Voltage Range | 304VAC ~ 456VAC | |||||||||
Frequency | 50Hz/60Hz ± 10% | |||||||||
TVSS | 40kA | |||||||||
BYPASS | ||||||||||
Nominal Voltage | 220VAC | |||||||||
Input Voltage Range | 165VAC ~ 275VAC | |||||||||
BATTERY | ||||||||||
Batery Voltage | 220VDC (Adjustable) | |||||||||
Cold Start | Yes | |||||||||
OUTPUT | ||||||||||
Power Factor | 0.8 | |||||||||
Nominal Output Voltage | 220VAC/230VAC/240VAC | |||||||||
Output Voltage Regulation | ±1% | |||||||||
Overload Capability | 110% continuous running; 125% for 10 min; >150% for 1 min | |||||||||
PHYSICAL | ||||||||||
IP Protection | IP31 (default), IP42 (Option) | |||||||||
Dimensions, D x W x H(mm) | 800 x 800 x 1800 | 800 x 1200 x 1800 | 800 x 1600 x 1800 | |||||||
Net Weight (Kgs) | 354 | 400 | 480 | 680 | 910 | 1010 | 1360 | 1620 | ||
ENVIRONMENT | ||||||||||
Operating Temperature | 0~ 40°C | |||||||||
Storage Temperature | -25°C ~ 55°C | |||||||||
Humidity | 0~95% (non-condensing) | |||||||||
Atitute | 1000m | |||||||||
MANAGEMENT | ||||||||||
Modbus RS-232/RS485 | Supports Windows® family, Linux and MAC | |||||||||
Dry Contacts | 5 outputs and 4 inputs | |||||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||||
STANDARD | ||||||||||
Safety | IEC62040-1-2017 | |||||||||
EMC Immunity | IEC61000-4-5 | |||||||||
EMC Emissions | IEC62040-2-2018 | |||||||||
Approvals | CE / CB/ Conformance testing / EMC / ROHS2 / Reach / YDT1095-2018 | |||||||||
* Product specifications are subject to change without further notice |