KEBOS POWER ,to continue a better life.
APD Lite 15U 60K is a modular UPS system comprised of 1 to 3 modules of 20KW. This UPS is easily upgraded by users through adding plug-and play 20kw power modules. Beside, this UPS system is stacked with battery pack as a tower for smaller footprint. It’s a perfect power solution for small-to-medium enterprise.
High efficiency online double conversion technology
Output power factor 1
Modular design lowers MTTR
Adjustable charging current
Built-in maintenance bypass switch for easy maintenance without interruptible
Graphic 5.7" LCD design for easy configuration
MODEL | APD Lite 15U-60 | ||||
---|---|---|---|---|---|
PHASE | 3-phase in/3-phase out | ||||
CABINET CAPACITY* | 60KW | ||||
BATTERY TYPE | External Battery | ||||
One Power Module Capacity | 20KVA/28W @ 30℃ | ||||
Max. Power Module No. | 3 | ||||
INPUT | |||||
Nominal Voltage | 3 x 208VAC/220VAC (3Ph+N) | ||||
Voltage Range | 156 ~ 253VAC at 70% - 100% load; 121 ~ 253VAC for <70% load | ||||
Nominal Frequency | 50/60Hz (Auto sensing) | ||||
Frequency Range | 40Hz ~70Hz | ||||
Power Factor | > 0.99 at 100% load, >0.98 at 50% load | ||||
Harmonic Distortion (THDi) | < 3% @ 100% load | ||||
OUTPUT | |||||
Nominal Voltage | 3 x 208/220 VAC (3Ph+N) | ||||
Voltage Regulation (Steady state) | ≦± 1% Typical (balanced load) ≦± 2% Typical (unbalanced load) | ||||
Voltage Regulation (Transient) | ≦± 5% Typical | ||||
Nominal Frequency | 50/60Hz | ||||
Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | ||||
Overload Capability | 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% | ||||
Harmonic Distortion | ≦ 2% THD (Linear Load) ≦ 4% THD (Non-linear Load) | ||||
Efficiency | Up to 92.5% | ||||
BATTERY / CHARGER | |||||
Nominal Voltage | +/- 120V (12V x 20 Pcs) | ||||
Floating Charge Voltage | 2.25V/Cell | ||||
Boost Charging Voltage | 2.35V/Cell | ||||
Temperature Compensation | Yes | ||||
Maximum Charging Current | 8A for each power module (User-djustable) | ||||
PHYSICAL | |||||
Cabinet Dimension (D x W x H) mm | 1000 x 514 x 763 | ||||
Net Weight (kgs) | 195 | ||||
ENVIRONMENT | |||||
Operation Temperature | 0 ~ 40℃ | ||||
Relative Humidity | 0 ~ 95% non-condensing | ||||
Altitude *** | <1000m for Nominal power | ||||
IP Class | IP 20 | ||||
MANAGEMENT | |||||
RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
*When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃. | |||||
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules. | |||||
***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m. |