KEBOS POWER ,to continue a better life.

APD Lite Modular 33 60KVA LV

APD Lite 15U 60K is a modular UPS system comprised of 1 to 3 modules of 20KW. This UPS is easily upgraded by users through adding plug-and play 20kw power modules. Beside, this UPS system is stacked with battery pack as a tower for smaller footprint. It’s a perfect power solution for small-to-medium enterprise.

  • High efficiency online double conversion technology

  • Output power factor 1

  • Modular design lowers MTTR

  • Adjustable charging current

  • Built-in maintenance bypass switch for easy maintenance without interruptible

  • Graphic 5.7" LCD design for easy configuration

Drag the table to right or left to view more.
MODELAPD Lite 15U-60
PHASE3-phase in/3-phase out
CABINET CAPACITY*60KW
BATTERY TYPEExternal Battery
One Power Module Capacity20KVA/28W @ 30℃
Max. Power Module No.3
INPUT
Nominal Voltage3 x 208VAC/220VAC (3Ph+N)
Voltage Range156 ~ 253VAC at 70% - 100% load; 121 ~ 253VAC for <70% load
Nominal Frequency50/60Hz (Auto sensing)
Frequency Range40Hz ~70Hz
Power Factor> 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)< 3% @ 100% load
OUTPUT
Nominal Voltage3 x 208/220 VAC (3Ph+N)
Voltage Regulation (Steady state)≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
Voltage Regulation (Transient)≦± 5% Typical
Nominal Frequency50/60Hz
Frequency Range (Synchronized range)46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Harmonic Distortion≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load)
EfficiencyUp to 92.5%
BATTERY / CHARGER
Nominal Voltage+/-  120V (12V x 20 Pcs)
Floating Charge Voltage2.25V/Cell
Boost Charging Voltage2.35V/Cell
Temperature CompensationYes
Maximum Charging Current8A for each power module (User-djustable)
PHYSICAL
Cabinet Dimension
(D x W x H) mm
1000 x 514 x 763
Net Weight (kgs)195
ENVIRONMENT
Operation Temperature0 ~ 40℃
Relative Humidity0 ~ 95% non-condensing
Altitude ***<1000m for Nominal power
IP ClassIP 20
MANAGEMENT
RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
*When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃.
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules.
***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.