KEBOS POWER ,to continue a better life.





LIO 4805/4810
• Modular design, up to 10 in parallel for capacity extension
• Built-in BMS, communication with power module via RS-485
• Life cycle : 8000 cycles at 25°C, 60% DoD
• Big discharging current design 75A(50Ah)/150A(100Ah)
• Finger proof design for external battery connector Flexible front and Rear installation
• Built-in breaker for safety operation • Easy capacity extension by paralleled
• Aluminum case LiFeO4 for cells, more safety and stable
• Customer-made protocol upgrade support
| MODEL | LIO 4805 | LIO 4810 | |
| CAPACITY | 2400Wh | 4800Wh | |
| PARAMETERS | |||
| NominalVoltage | 48VDC | ||
| FullChargeVoltage(FC) | 52.5VDC | ||
| FullDischargeVoltage(FD) | 34.5VDC | ||
| TypicalCapacity | 50Ah | 100Ah | |
| MaxContinuousDischargingCurrent | 75A | 150A | |
| MaxPeakDischargingCurrent | 100A | 150A | |
| BatteryConnectorMaxcurrent | 75A | 75A+75A | |
| Protection | BMS,Breaker | ||
| ChargeVoltage | 52.5±0.1V | ||
| MaximumChargeCurrent | 50A(0.5C) | 100A(0.5C) | |
| StandardChargeMethod | 0.2CCC(Constantcurrent)chargetoFC, | ||
| CV(ContstantvoltageFC)chargetillchargecurrentdeclineto<0.05C | |||
| InnerResistance | <20mohm | ||
| PHYSICAL | |||
| Dimension,DxWxH(mm) | 630x438x86 | 630x438x133 | |
| NetWeight(kgs) | 28.2 | 48.5 | |
| INDICATORS | |||
| LED | BatteryStatus,Batterylevel,Batteryfault,Alarm | ||
| ENVIRONMENT | |||
| Operating Environment | Charge | 0°C~50°C | |
| Discharge | 0°C~50°C | ||
| StorageTemperature(At50%SOCandspecifiedtemp,recoverablecapacityin%vstime/50%) | <18months:-20°C~25°C | ||
| <3months:25°C~45°C | |||
| <1months:45°C~60°C | |||
| 20°C±5°Cistherecommendedstoragetemperature | |||
| MANAGEMENT | |||
| Communication | RS485port(RJ45),extensionport(RJ11) | ||
| Certifications | UN38.3,IEC62619 | ||
| DesignLife | >10years@25ºc | ||
| Lifecycle | >4500@25ºC | ||