AP Lite series Modular Online UPS with high efficiency online double conversion technology, Output power factor 1.0.
Expanding your AP Lite Modular UPS is easy with the UPS’ intelligent system. It automatically detects connected modules and fully configures itself for parallel operations.
Modular design lowers MTTR Adjustable battery numbers and Adjustable charging current, it Built-in maintenance bypass switch for easy maintenance.
High efficiency online double conversion technology
Output power factor 1
Modular design lowers MTTR
Adjustable battery numbers
Adjustable charging current
Built-in maintenance bypass switch for easy maintenance without interruptible
Graphic 5.7" LCD design for easy configuration
MODEL | AP Lite 15U-60 | AP Lite 15U-90 |
---|---|---|
PHASE | 3-phase in/3-phase out | |
CABINET CAPACITY* | 60KW | 90KW |
BATTERY TYPE | External Battery | |
One Power Module Capacity | 20KVA/20KW | 30KVA/30KW or 20KVA/20KW |
Max. Power Module No. | 3 | |
INPUT | ||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | |
Voltage Range | 305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load | |
Nominal Frequency | 50/60Hz (Auto sensing) | |
Frequency Range | 40Hz ~70Hz | |
Power Factor | > 0.99 at 100% load, >0.98 at 50% load | |
Harmonic Distortion (THDi) | < 3% @ 100% load | |
OUTPUT | ||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | |
Voltage Regulation (Steady state) | ≦± 1% Typical (balanced load) ≦± 2% Typical (unbalanced load) | |
Nominal Frequency | 50/60Hz | |
Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |
Overload Capability | 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% | |
Harmonic Distortion | ≦ 1.5% THD (Linear Load) ≦ 4% THD (Non-linear Load) | |
Efficiency | Up to 94.5% | |
BATTERY / CHARGER | ||
Nominal Voltage | +/- 216V (12V x 36 Pcs) | |
Maximum Voltage | +/- 240V (12V x 40 Pcs) | |
Minimum Voltage | +/- 192V (12V x 32 Pcs) | |
Floating Charge Voltage | 2.25V/Cell | |
Boost Charging Voltage | 2.35V/Cell | |
Temperature Compensation | Yes | |
Maximum Charging Current (Per Power Module) | 8A for 30KW power module (User-djustable) 6A for 20KW power module (User-adjustable) | |
PHYSICAL | ||
Cabinet Dimension (D x W x H) mm | 1000 x 515 x 760 | |
Net Weight (kgs) | 182 | 183.5 |
ENVIRONMENT | ||
Operation Temperature | 0 ~ 40℃ | |
Relative Humidity | 0 ~ 95% non-condensing | |
Altitude *** | <1000m for Nominal power | |
IP Class | IP 20 | |
MANAGEMENT | ||
RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | |
Optional SNMP | Power management from SNMP manager and web browser | |
STANDARDS | ||
Safety | IEC/EN 60950-1; IEC/EN 62040-1 | |
EMC | IEC/EN 62040-2 Category C3 | |
*When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃. | ||
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules. | ||
***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m. |
Model | Description | Dimension DxWxH(mm) | Weight (kg) |
---|---|---|---|
PM-30HV | 3P/3P 30KVA/30KW power module | 650x440x132(3U) | 34.5 |
PM-20HV | 3P/3P 20KVA/20KW power module | 650x440x132(3U) | 34 |
Battery Cabinet | 120 pcs of 12V9Ah batteries | 1000 x 514 x 610 | 387 |